METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-100 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
4. Subsystem devices, conduits, trays, distributed antenna cables and other
fire/live safety communication installations CANNOT be mounted in the
proximity or the train dynamic envelope and passenger emergency egress,
such as safety walks and emergency exits. For example, subsystem
devices, conduits, trays, distributed antenna cables and other fire/live safety
communication cannot mounted anywhere directly above the LRV
pantograph.
5. Subsystem devices, conduits, trays, distributed antenna cables and other
fire/live safety communication installations shall be not conflict with other
tunnel installations and shall not come closer than 6 inches to the vehicle
dynamic outline at any point in the tunnels.
9.5.4 Communications Power System
All Stationery Systems Equipment shall be powered from stationary battery/rectifier
or UPS plants, as applicable.
A. Batteries
Batteries in yards and ROC battery rooms shall be gel sealed batteries, non-
outgassing storage type of long-duration/low-rate. .
B. Rectifiers
Rectifiers shall be dual and load-sharing, with each rectifier capable of supplying
full equipment load while recharging a fully discharged battery.
C. Battery Racks
Battery racks shall be not larger than two-tier configuration, and shall be
constructed with seismic bracing in accordance with the UBC Requirement For
Seismic Zone Four.
D. Voltages
Battery/rectifier plant voltages shall be as follows:
Battery voltages for other communications equipment shall be compatible with
the equipment requirements.
E. Sizing
Battery sizing shall provide full load for a minimum 4 hours of main AC power
outage.
F. Recharge Time
The recharge time of a battery plant shall not be greater than four times the
discharge time period, e.g., discharge 4 hours, recharge 16 hours.