METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-122 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
transmit information via an optical fiber of the fiber optic transmission link.
Sources shall be capable of operation at a data rate compatible with the type
of data transmitted.
3. All local distribution cables shall be placed in galvanized rigid steel conduit
or totally enclosed raceway. Other Materials are acceptable only for
backbone cable in main duct backs when encased in concrete or buried
under a minimum of 24 inches of cover.
4. All outside plant and tunnel metallic distribution cables shall be surge
protected at all main and subsidiary distribution frames and at all cable
terminals. Protection shall be by 3-electrode fail-short gas tube or electronic
protectors.
5. Optical Cable
All outside main backbone optical fiber cable shall be gel-filled and armored
for rodent protection. Sufficient fiber strands shall be provided to support the
CTS subsystem plus future extensions and 25% spare. Safety-critical
signals will be backed up by another independent transmission path or
means.
6. Backbone and Local Distribution - Metallic Pairs
Local CTS distribution for voice and data circuits shall be twisted pair, using
standard telephone cable color coding.
All outside plant cables shall be 22 AWG minimum, gel-filled, foam/skin
insulated conductors that meet Rural Electrification Administration (REA)
PE-89 and shall be gopher-protected. All cables shall be sized for initial
requirements plus 25%. No outside plant cable shall be less than 12 pairs.
All main riser cables shall be 22 AWG minimum, and shall meet REA PE-22
o PE-89. No cable shall be less than 12 pairs.
Inside wire from distribution terminals to instruments shall be 22 AWG
minimum, and have a characteristic impedance of 105 ohms + 15%. All
telephone instrument and jack appearances shall be served with a minimum
of three (3) dedicated pair.
All outside main and riser-paired cables shall be shielded.
REA PE-39 cables shall not be used as a substitute for PE-22 or PE-89
cables.
9.11 SUPERVISORY CONTROL AND DATA ACQUISITION
9.11.1 General
The Supervisory Control and Data Acquisition (SCADA) subsystem shall provide
supervisory control of the Train Control (TC) system, auxiliary and traction power,
the Environmental Control System (ECS), facilities, and other systems and