METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-125 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
8. An emergency condition shall immediately be displayed on the operating
displays to permit monitoring of device actions by the operator. In the event
that a sequence of actions has been initiated, the appropriate devices shall
flash until the sequence has been completed.
9. A horn/strobe device shall be activated by Fire/Life Safety critical alarm
indications as the SCADA also serves as a remote fire alarm annunciator.
9.12 EMERGENCY MANAGEMENT PANEL
9.12.1 General
An Emergency Management Panel (EMP) shall be provided at designated locations
at underground and aerial stations (Reference: Fire/Life Safety Criteria). Each EMP
shall be equipped with controls alarms, and status indications, as applicable, for:
Emergency Ventilation Systems
Fire Detection and Suppression Monitoring
• Gas Detection
• Intrusion Detection
• Seismic Detection
Public Address System
• Escalators
• Elevators
Each EMP shall be equipped with the following communications circuit access:
Priority Access to local PA system
Two ETELs (wall phones with outside dialing)
Evacuation system activation
Remote annunciator for the fire alarm control panel
In addition, each EMP should have a designated space for EMP as-built map books
and emergency ventilation procedure books (as applicable).
9.12.2 Operation
When activated, the EMP shall have control priority over central control of the
emergency ventilation. Alarms and indications shall be reported to the EMP and to
central control regardless of which entity is in control.
Underground EMP shall have the capability of controlling multiple ventilation zones
served by separate F&EM PLCs. Only one EMP or ROC shall have control over a
ventilation zone
The location of EMPs and their ventilation zone assignments shall be coordinated
with the local Fire Department having jurisdiction.
9.12.3 Design Criteria
The EMP shall be an intuitively operated touch screen (with back-up
Seitenansicht 129