METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-129 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
i. Encoding terminals shall be provided for the encoding of key cards with
employee name, department, badge number, SCN and zone code.
Encoding terminals shall encode key cards singly or in multiple.
j. Encoded key cards shall be impervious to magnetic fields, dirt, water, oil,
embossing, laminating and damage by scratching.
k. Vandal-resistant, weatherproof, proximity type card readers shall be
located at traction power substations, passenger station public areas,
main entrance rolling grilles to the passenger stations, TC&C rooms,
communications equipment rooms, Yard Control Towers, auxiliary power
rooms, electrical rooms, sprinkler valve rooms, and station auxiliary
power rooms.
9.13.3 Design Criteria for Enclosed Space
A. Functional Requirements
Detection of intrusion shall be reported to ROC via CTS
1. This subsystem of IDS shall be capable of detecting and recording intrusion
by movement and vibration on the track way at station platforms, along
perimeter fencing along the right-of-way, and to tunnel entrance areas.
2. The subsystem shall integrate with security (CCTV) cameras and video
recorders to pan, tilt and zoom to the location of detection.
3. The subsystem shall be immune to EMI, RF emissions, and lightning.
4. The subsystem software/firmware shall be capable of automatically
generating both visual (through CCTV) and audible alarms to Observers at
ROC.
9.14 FIRE ALARM SYSTEM
9.14.1 General
The fire alarm system shall generally consist of a fire control panel, smoke & heat
detectors, monitor modules for water flow and valve tamper switches, monitor, relay,
and control modules, and audible and visual notification devices.
If there is a fire, the fire alarm system shall provide alarm annunciation, and as
applicable, automatic fan and damper shutdown, elevator recall and shunt trip, fire
suppression activation, and evacuation by zone.
9.14.2 Design of the Fire Alarm System
A. Fire alarms, supervisory alarms, and trouble alarms shall be monitored at the
ROC through the SCADA system.