METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-141 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
6. The Rectifier Unit and the DC Distribution Switchgear shall be provided with
DC ground protection of a high resistance type for the Heavy Rail TPSSs.
The Rectifier Cubicle and the DC Distribution Switchgears will be insulated
at 1,000 V level from the floor where they are installed and shall be
respectively provided with separate individual ground relays. Ground faults
on the Rectifier Unit shall trip the associated AC breaker, as well as the
associated positive breaker. Ground faults on the DC Distribution Switchgear
shall trip the respective AC breaker(s), positive breaker(s), and all its feeder
breakers.
7. The DC feeder circuit breakers of adjacent TPSS connected to the same
OCS/Third Rail section shall be provided of a transfer trip system. Each
breaker shall send transfer trip signal to the adjacent breaker whenever a
fault is detected, including over-current, rate of rise, and ground faults. The
over-current and rate of rise transfer trip signals shall allow the re-closure of
the adjacent breaker, while the ground fault transfer trip signals shall lock-
out the adjacent breaker, without any re-closing attempt.
8. A Negative Ground Device shall be provided to automatically connect the
negative bus of each substation to ground, in case the voltage to ground
exceeds a pre-set value.
9. Surge Arrestors shall be provided on the load side of each DC feeder
breaker, and shall be connected with insulated cables to grounding rods
independent from the main substation rounding grid.
10. The positive breakers shall be provided with reverse current protection.
11. All Substations shall be provided with a grounding grid with a minimum of 5
ohms resistance to ground. The grounding grids shall also meet the
requirements of the Utilities and provide safe step-and-touch potentials
according to the applicable Codes and Standards. All non-current carrying
structures and equipment enclosures shall be solidly connected to the
grounding grid, except the DC Enclosures for the rectifiers and DC
Switchgears, as required by their specific method of grounding – low
resistance or high resistance.
12. The negative return of the Mainline and Yard traction power system shall not
be grounded intentionally at any point, either at the substations, feeder
cables, or at track level.
13. The Shops shall have separate and independent TPSSs solidly grounded
and isolated from the Yards on the positive side by non-bridging section
insulators, and on the negative side by Rail Insulated Joints, properly aligned
with the respective section insulators.
G. Substation Operation
All TPSSs shall be designed for unattended operation and remote control by the
Rail Operation Control-ROC. All circuit breakers shall be able to be both locally
and remotely operated and a Local/Remote Switch shall be provided at each
TPSS. Open/close commands and open/close indications shall be provided. All
protective and supervisory devices shall be individually alarmed both locally and
remotely. Voltage and current meters shall also be provided locally and/or