METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-142 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
remotely. A list of local and remote controls, indications, and alarms shall be for
Metro approval for each specific TPSS design in order to provide its safe and
reliable operation. The interface with the remote operation at ROC shall be
coordinated d with the respective SCADA system connected to the Rail
Operations Control-ROC.
H. Auxiliary Equipment
1. Lighting
Indoor lighting shall be provided by fluorescent fixtures. Design shall provide
for minimum maintained lighting levels of 30 foot-candles vertical, average.
Such lighting shall be located so as to illuminate satisfactorily the vertical
surfaces of equipment such as switchgear and transformer rectifier units.
Locations of lighting fixtures shall be coordinated to avoid interference with
overhead raceways or other major wiring and shall not be directly above
switchgear, rectifiers, or transformers. Outdoor lighting shall be provided by
energy efficient lamp fixtures with built-in photocell control. Design shall
provide a minimum illumination level of one foot-candle at ground level. The
general lighting shall be controlled from switches located near each access
door.
2. Emergency Lighting
Substations shall be provided with emergency lighting from individual self-
contained, maintenance-free units, with one or more lamps mounted on the
equipment and a relaying device arranged to energize the lamps
automatically on failure of AC power. Batteries shall have 1-1/2 hour
minimum cut-off capacity from fully charged state and shall have testing
means accessible from outside. Sufficient fixtures shall be provided to
illuminate egress paths as required by code(s).
3. Convenience Outlets
Duplex convenience 20 amp outlets shall be located approximately 25 feet
apart around the interior walls of the substations And within 10 feet of AC
and DC protection relays (for testing equipment purposes).
4. Auxiliary Equipment
Other auxiliary equipment shall include, but not be restricted to, Batteries
and UPSs for DC and AC control power and essential loads, AC and DC
distribution panels, Local Panel Annunciators- LAPs, Smoke Detectors and
Fire Control Panel-FCP, intrusion detection system, and provision for stray
current corrosion measurements and/ negative return drain connections
I. Construction and Equipment Arrangement
1. Underground Substation rooms or outdoor housing shall have adequate
area to permit placement of electrical equipment and ancillary components
of any manufacturer. Relative spacing and positioning of each equipment
unit shall permit the removal, replacement, or maintenance of such unit
without the necessity of moving other units. The arrangement of the