METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-3
Metro Baseline Re-Baseline: 04/20/10
closure. However the design shall accommodate fused wetted contacts where
necessary.
3.2 ASSEMBLY
A Components within assemblies shall be neatly arranged and fastened securely to
the assembly subpanel with nonflammable fasteners. The use of plastic wire
troughs shall be subject to review and approval. Metal wire clamps shall have
insulating inserts between the clamps and the wiring. Wiring between stationary
and movable components, such as wiring across door hinges or to components
mounted on extension slides, shall allow full movement of the component without
bending or chafing the wiring.
B Each assembly shall include suitable signal and safety ground networks. The
safety ground shall be isolated from the signal ground and shall connect to the
ground (green) wire of the ac power input or to a dedicated ground wire for DC
powered assemblies. The signal ground shall terminate at a separate stud
connection, sized for connection of a lugged No. 2/0 AWG ground wire. Use of
the enclosure frame, skins, or chassis mounting hardware for the ground network
will not be considered acceptable. Assembly grounding shall be subject to
approval.
C The assembly shall have four distinct functional areas: power distribution, logic
controller, auxiliary equipment and I/O.
D Cables and wires shall be neatly arranged and secured/fastened to permit
maintenance access to all equipment without the need to disturb any wire or
cable.
E Adequate space shall be allocated for routing and management of I/O module
cable.
F Space for routing and management of field interface cable shall be provided at
each side of the I/O section. 2”x4” (width x depth) metal vertical cable
management brackets shall be installed along each side of the I/O section for
securing field cables of up to 1” diameter.
G The auxiliary equipment area shall have a minimum dimension of 8”x16”.
H The I/O area shall include reserved space for installation of optional indicating
fused feed thru terminal blocks for distribution of wetted contact control outputs.
Space for at least 33 terminal blocks shall be provided.
I The power distribution area shall include reserved space for mounting of an
auxiliary power supply and fused load circuit terminal blocks. Incoming power
terminal blocks shall have a spare line, neutral and ground terminal block
reserved for installation of the auxiliary power supply.
J All panel indicators shall be visible from the front of the assembly subpanel.