METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-4
Metro Baseline Re-Baseline: 04/20/10
K All assembly components, cables, and appurtenances shall be accessible from
the front of the assembly.
L Access to the rear of the assembly for any maintenance purpose shall not be
required.
M Provide an appropriately rated breaker for incoming power to serve as a main
disconnect.
N Provide a dedicated terminal block for distribution of incoming power, ground and
neutral/return. The use of 120VAC power cords or plug-in transformers shall be
prohibited. At least two spare circuits shall be provided.
O Provide a dedicated terminal block for assembly 24VDC power distribution and
return with one indicating fuse for each distribution circuit.
P Power distribution shall utilize bus bars. No daisy chain wire distribution shall be
permitted.
Q Supply, return and ground shall use physically separated terminal block sections.
R Provide approved vendor pre-manufactured I/O field interface module (IFM)
terminal blocks for all field wiring or other terminal block assemblies. Each IFM or
I/O terminal block shall be connected to its associated PLC I/O module using a
vendor pre-manufactured cable.
S All assembly wiring shall be secured with panel mounted guides and or other
approved wire management devices.
T All assembly components shall be professionally labeled in accordance with shop
drawings using an approved manner.
U Any terminal block section greater than 48VDC shall have a warning label.
V Multi-conductor cables shall be used to interconnect the RTU discrete I/O
terminal blocks to the Main Distribution Frame or board (herein referred to as the
MDF). Dedicated blocks shall be assigned on the MDF for termination of RTU
cables.
W Each discrete I/O field cable between the RTU and the MDF shall be a minimum
of 25-pair and shall be sufficiently rugged for direct routing in overhead cable
trays.
X All field interface connections shall terminate on the MDF. Outside/external cable
shall terminate on building entrance protection blocks. Subsystem cables within
the RTU communications room/cabinet shall terminate on regular interface
blocks. Cross connect wire shall be used to interconnect each field interface to
the SCADA interface terminal blocks on the distribution board/frame.