METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-5
Metro Baseline Re-Baseline: 04/20/10
3.3 REMOTE TERMINAL UNIT OPERATION
A Power-up and Initialization
1. Turning the RTU on or off shall be accomplished by operating a single
breaker installed on the assembly. Operating this breaker shall control
power to the entire assembly.
2. Upon application of power the RTU shall normally power up, initialize and
achieve a normal operating state without the need for any manual
intervention.
3. The RTU initialization shall clear all system fault registers before initiating
the system diagnostics.
B Diagnostics
1. The RTU shall perform continuous diagnostics to report the following
conditions:
a. CPU faults
b. Module faults
c. Remote I/O link status
d. Local serial link status for communications based subsystem
interfaces
2. The RTU shall increment a health register (RTU Health Register) once per
second to indicate to SCADA that the PLC is in a normal run mode and is
executing the ladder logic. The register shall reset to zero when a value of
255 is reached.
3. The RTU shall monitor a health register that is updated by the SCADA
system (SCADA Communications Watchdog). If the register fails to update
for 30 seconds the RTU shall declare the SCADA system as offline. This
status shall be reflected in the first contact of the first discrete output
module. The contact shall be closed if SCADA is online and shall be open if
SCADA is not online or the PLC is failed.
4. The RTU shall monitor control/wetting voltage in the 1
st
input point of the
first discrete input module.
5. The RTU shall report a chassis summary blown fuse alarm for each fused
terminal block starting at the 2
nd
input point of the first discrete input
module.
C SCADA Communications
1. The Cable Transmission System (CTS) shall provide an Ethernet LAN
dedicated for SCADA communications. The LAN shall allow all RTU to be
accessed from a single port on the CCF SONET without the need for any