METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-11
Metro Baseline Re-Baseline: 04/20/10
6. Fuse status shall be indicated in a consistent manner for each fuse except
where otherwise approved.
C Circuits
1. Main Incoming and Supply Circuits
a. A “main” breaker shall be installed to protect the main distribution
terminals and to serve as a power disconnect.
b. A fuse shall protect each power feeder circuit.
c. The fuse shall be rated to protect the circuit wiring and permit full load
of each distributed circuit.
2. I/O Module Common voltage Supply Circuits
a. Common supply voltage shall be individually fused for each input and
output module.
b. Each fuse shall be an indicating type that is sufficiently rated to allow
all inputs or outputs on a module to be active simultaneously and be
rated lower than the main supply fuse so that a fault on a single point
only affects a single module.
3. Control Voltage
a. The power supply shall be 24VDC output, fully enclosed modular unit
for panel or DIN rail mount. The PLC chassis power supply may be
used for control voltage if the rating is sufficient to drive the maximum
PLC chassis configuration and interface module relays for all
indicating and control points in their active state.
b. The power supply shall include automatic load current / short circuit
protection.
c. The voltage power supply output feeds shall include foldback circuitry
such that after a fault is removed from the line the voltage level shall
be automatically restored to its proper operating level.
D RTU Modular Components (general)
1. The RTU components shall be based on a family of processors that are
compatible with the existing Metro SCADA system, having at least 10,000
units in service in North America, with local sales and service available
within 50 miles of Los Angeles.
2. Module components shall be available from the RTU CPU vendor as well
as certified third-party manufacturers to support a wide variety of input,
output, and interfacing requirements.
3. Operating temperature 0-50 degrees Celsius with exception of modular
communications equipment.