METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-12
Metro Baseline Re-Baseline: 04/20/10
4. Communications equipment operating temperature 0-40 degrees Celsius.
5. Humidity 5-95% non-condensing
6. Noise immunity NEMA Standard ICS 2-230
7. Dielectric withstand 1500VDC (UL 508, CSA C22.2 No. 142)
8. Flammability and Electrical ignition UL94V-0
9. Removable barrier-type terminal blocks or connectors to allow module
replacement without the need to disturb wiring
10. Self-locking tabs to permit installation and removal of chassis modules
without the need for tools
11. Indexed plugs and connectors to prevent incorrect insertion
12. Continuous overload protection of 200V between any interface terminal and
ground.
E RTU CPU
1. CPU memory shall be of adequate capacity to execute the Contractor
provided firmware with at least 25% of the memory unused.
2. Typical scan time 0.9 ms/K
3. Supports online programming and editing
4. The CPU shall include one Ethernet port with a protocol supported by
available OLE For Process Control (OPC) vendors.
5. The CPU shall include one master/slave serial port.
6. Local key switch mode selector for run, program, and remote modes.
7. System protection options shall be included for: program files, data tables,
input/output forces, CPU run mode (requires insertion of a key).
F SCADA Communications
1. The RTU shall support Ethernet communications using a protocol
compatible with the existing Metro SCADA system.
2. The SCADA communications shall be subject to approval.
3. The communications shall support efficient transfer of indication and control
information.
4. It shall be possible (and be supported by OPC vendors) to pack discrete
indications and controls into word based arrays and subsequently index
specific bits out of each register word.