METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix B
DE304.09 Appendix 9B-7 Revision 1 : 05/09/12
Metro Baseline Re-Baseline: 04/20/10
1.6.1.12 Facilities Monitoring
Corrosion control system alarm
Seismic detection minor (0.1G) alarm
Seismic detection major (0.2G) alarm
Seismic detection system trouble
Sump/ejector pump panel alarm
Sump/ejector pump tank service required alarm
Sump/ejector pump running alarm
Sump/ejector pump tank high level alarm
Sump/ejector pump tank high level, overflow alarm
Sump/ejector running with no flow alarm
1.6.1.13 Uninterruptable power supply
General trouble
Manual bypass alarm
On battery alarm
Low battery / imminent shutdown
Hydrogen warning and explosive level alarm (where required)
1.6.1.14 Emergency Ventilation and Booster Fan
Air flow indication for each direction and speed
Supply on, motor control indication
Exhaust on. Motor control indication
High speed on, motor control indication
Supply on, exhaust on, and standby control
High speed on and off control
Bearing trouble alarm
Winding temperature alarm
Vibration alarm
Fan control mode indication
Fan auto mode disable and enable indication
Fan auto mode indication
Fan and track damper supply or control power fail
Fan and track damper open and closed indication
Fan and track damper open and close control
1.6.1.15 Under Platform and Overhead Exhaust Fan
Control mode indication
Fan on indication (motor contactor)
Air flow indication
Fan on and off control
1.6.1.16 Elevators
Position indication for each level
Trouble indication
Hall call indication for each level
Lockout active indication