METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix B
DE304.09 Appendix 9B-8 Revision 1 : 05/09/12
Metro Baseline Re-Baseline: 04/20/10
Fire recall active indication
Emergency mode indication
Remote call control for each level
Lockout activate and cancel control
One-trip control
1.6.1.17 Escalators
Running up indication
Running down indication
Key resettable trouble indication
System trouble (non-resettable) indication
1.6.1.18 Fire Detection
All Stations:
Fire system trouble
Fire system alarm
Fire supervisory (also summarizes ETEL trouble at FACP)
ETEL trouble (one per ETEL via direct SCADA RTU interface)
Aerial Stations and Fire Protection where applicable:
Pre-action tamper SW TC&C Rm. Supv.
Flow xxx alarm (one per coverage zone)
Fire xxx Alarm (one per room or coverage zone for smoke, heat, manual pull or flow
detection)
Manual pull xxx alarm (one per coverage zone in the public area)
Tamper switch xxx Supv. (one per valve room location)
Pre-action low pressure xxx Supv. (one per coverage area)
Pre-action activation (one per system)
1.6.1.19 Fire Suppression
Deluge active alarm
Deluge release system trouble
Water flow switch alarm
Pre-action release alarm
Fire pump supervisory alarm
Fire pump system trouble
1.6.1.20 Gas Detection
Probe gas minor level alarm
Probe gas major level alarm (where required)
Probe gas evacuation level alarm
Probe gas reading indication
Probe trouble or disconnected alarm
Gas control unit trouble alarm
Gas control unit in calibration alarm