METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-91 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
B. The telephone service shall include emergency, maintenance, administrative
telephones, and passenger assistance intercom at passenger stations, wayside,
the ROC, and the Yard, served by Metro private telephone system. In keeping
with regulatory practice, all emergency and patron assistance telephone
communications shall be recorded.
C. Public address (PA) services shall provide a fully supervised PA subsystem at
each passenger station, the Yard and shop buildings with access and control
from various locations. The PA subsystem shall be used to provide routine
announcements and emergency warning information. The PA subsystem shall
at the Yard and Shop buildings shall allow announcements from designated
Yard and Shop phones to be directed to any one or multiple simultaneous
zones.
D. Closed circuit television (CCTV) shall provide means of surveillance of
passenger stations, the vehicle storage area, and other areas as required.
E. The cable transmission subsystem (CTS) shall provide the primary means of
information transmission between the ROC, passenger stations, wayside
facilities (as required), and the Yard and Shop.
F. The Supervisory Control and data acquisition (SCADA) subsystem shall provide
a master control station at the ROC and wayside interfaces for remote
monitoring and control of train operations, traction power and station and
wayside facilities.
G. Intrusion Detection and Controlled Access
The Intrusion Detection and Controlled Access shall provide a master station at
the ROC and remote wayside devices for remote monitoring and control of
secure facilities access.
H. Rail Operations Control (ROC)
The ROC subsystem shall provide unique equipment to support other systems,
such as traction power, train control (TC), and the Environmental Control
System (ECS). Included in this location are data processing equipment, control
consoles, radio support interface equipment, Metro private telephone system,
hub equipment for CTS, voice logging recorders, video monitors and recorders,
data recorders, displays, and control panels.
I. Gas Monitoring system (For underground systems)
A fully supervised gas monitoring subsystem shall be installed as required by
results of soil sample test conducted during station construction and compliance
with the Environmental Impact Study (EIS). Gas monitoring controller
equipment, integrated with the station fire system and ROC SCADA, shall be
located in the train control and communications (TC & C) room and
communicate with sensor heads installed at designated locations as necessary
for the detection of the presence of specific gases at alarm concentrations.