17 Smart-UPS On-Line, 230 V, 1 kVA to 20 kVA Technical Specifications 990-4769
Battery Specifications
UPS VA
1000
2000
2200
3000
5000
6000
8000
10,000
15,000
20,000
Type
Maintenance-free valve-regulated lead-acid battery with suspended electrolyte, leak-
proof
Replacement
Battery
RBC31
RBC44
Included
Replacement
Battery Cartridges
1
2
4
Hot-Swappable
Yes
User-Replaceable
Yes
Battery Voltage,
Vdc
48
192
+/- 192
Battery Amp-Hour
Capacity
9 Ah
5.1 Ah
Battery Charger
Power
100 W
400 W
800 W
Variable, up to
3 kW
Recharge Time 0%
to 90%
3
hrs.
4
hrs.
2.5 hours
2.2 hours
2.5 hours
Automatic Self-
Test
At turn-on, every 7 days, or every 14 days (user-selectable)
Typical Battery
Life
3 to 5 years
Extended Runtime
Option
Yes
Battery Material Safety Data Sheet
Note: For Material Safety Data Sheet (MSDS), go to
http://nam-en.apc.com/app/answers/detail/a_id/564/kw/msds.