METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix A
DE304.09 Appendix 9A-14
Metro Baseline Re-Baseline: 04/20/10
8. Input signals shall be isolated from the backplane.
9. The A/D converter shall provide a minimum precision of 4096 steps plus
one sign bit.
10. Continuous automatic calibration.
11. Common mode rejection shall be at least 50db at 50 and 60Hz.
12. Isolation of 500VAC/VDC withstand for one minute.
4.3 SUBPANEL
A All materials used in the assembly including cable insulation or sheathing, wire
troughs, terminal blocks, shall be made of flame retardant material and shall not
produce toxic gasses under fire conditions (see NFPA 75). The use of PVC shall
require approval. Each individual device shall be constructed so that by limiting
combustible materials, or by use of enclosures, fire is not likely to spread beyond
the device in which the source of ignition is located. Assemblies of floor standing
equipment having external surfaces of combustible materials of such size that
might contribute to the spread of an external fire shall have a flame spread rating
of 50 or less (see NFPA 255, Method of Tests of Surface Burning Characteristics
of Building Materials). (Note: UL listed equipment or equipment meeting the
requirements of UL standard number 478 will be considered as meeting the
above requirements.)
B The subpanel shall be metal, finished on all sides to resist corrosion in a marine
environment. The panel thickness shall be such that there is no deformation of
the mounted subpanel while performing maintenance and assembly procedures.
The panel material shall support drilling and taping of screws for installation of
components and fasteners by others.
C The maximum dimensions of the assembly including subpanel, all components,
cables, bending radius and connectors shall require no more than 22” wide x 20”
deep x 70” high for installation.
D The assembly shall be suitable for mounting on a standard 19”
telecommunications rack or plywood backboard.
E Mounting and enclosure shall be site specific adhering to all environmental and
other design criteria.
4.4 CABLES WIRES
A Each cable shall be labeled at both ends in a manner consistent with Contractor
drawings.
B Labels shall use non-fading, permanent marking, and can be read without
disruption of any component.