METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-149 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
locate a gap in the normally accelerating zone, and at gap locations other
than at stations, the gap shall be of special design to prevent interruption of
power to trains during normal operation.
D. Overhead Contact System (OCS)
1. General
a. The OCS includes the Catenary system, the physical support structure
and the associated feeder system.
b. The Catenary system consists of the conductors, including the contact
wire and supporting messenger (where used); in-span fittings; jumpers;
conductor terminations; and associated hardware located over the track
and from which the vehicle draws power by means of physical contact
between the pantograph and contact wire. The Catenary system shall
provide for satisfactory current collection under all operating conditions.
See Section 10 Operations.
c. The physical support structure consists of foundations, poles, guys,
insulators, brackets, cantilevers, and other assemblies and components
required to support the Catenary system in the appropriate configuration.
The support system shall support the Catenary system in accordance
with allowable loading, deflection, and clearance requirements. The
supports throughout the system shall incorporate double insulation in
accordance with the requirements of CPUC General Order 95. Structure
grounding and bonding measures shall be provided in accordance with
corrosion control and safety requirements.
d. The feeder system consists of the feeder conductors, jumpers;
disconnect switches, ductwork, and associated hardware that feed the
power to the Catenary system. The feeder system in combination with
the Catenary system shall provide for the supply of traction power to the
vehicles within the allowable voltage limits. The design for all feeders
and jumpers shall be sized; based on their respective current carrying
capabilities, the wires to which they are attached, and the power
requirements of the system.
e. Electrical continuity shall be provided in the OCS from substation to
substation. At the substations, the Catenary system continuity shall be
sectionalized to provide isolation of each electrical section. An
arrangement providing continuity and flexibility for sectionalization of the
OCS while any mainline or substation is undergoing repair or
maintenance shall be incorporated. This will be accomplished through
the application of both electrically and manually operated outdoor and
indoor types of disconnect switches as required for operations and
maintenance. Between substations the continuity shall be accomplished
by insulated or un-insulated Catenary overlaps with continuous jumper
arrangements, or section insulators with jumpers and disconnect
switches and jumper arrangements.
f. The design of the overhead contact system shall be based on technical,
operation and maintenance requirements, aesthetics, and economic