METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
Appendix B
DE304.09 Appendix 9B-3 Revision 1 : 05/09/12
Metro Baseline Re-Baseline: 04/20/10
RTU ID – The RTU ID shall identify the RTU that contains the point.
IO Location – The IO Location shall identify the physical location of the field wiring
interface terminal cabinet.
IO Type – The IO Type shall specify if the point is an indication or control.
Point States – Point States shall provide information for encoding/decoding PLC register
and bit values.
o Define the meaning of each zero (0) and one (1) etc. for discrete values.
o Conversion to engineering units for analog values
RTU module assignment – RTU Module and point assignment.
RTU module address – Register/bit assignment of the physical I/O
Gateway address – Internal register/bit assignments for I/O interfaced through
communications gateways.
SCADA address – Register/bit assignment within the RTU for the SCADA interface. All
I/O shall be buffered to internal RTU memory.
RTU terminal – Terminal block and Terminal numbers for field cable termination within
the RTU or remote I/O.
SCADA MDF terminal – Terminal block and terminal numbers for field cable terminations
within the main distribution frame or board.
Field MDF terminal – Terminal block and terminal numbers for the device cable
termination within the main distribution frame or board.
1.6.1.1 SCADA Internal, Assembly and Remote I/O Diagnostics
PLC health register counter (watchdog)
CPU online indication (for redundant CPU systems)
CPU available indication (for redundant CPU systems)
Loss of module voltage alarm
Loss of field control voltage alarm
Summary fuse alarm
Redundancy component failure alarm (one for each redundancy component)
RIO link fail (for each RIO link)
Data link fail (for each local data link)
SCADA communications health register (watchdog)
Sensing voltage fail alarm
1.6.1.2 Train Control and Operations
Track occupancy indication for each track circuit and overlay
Traffic direction indication and request indication for each block at each end of
interlocking and at each block section. Each direction shall be indicated as a separate
point.
Platform service mode control and indication for each terminal platform or turnback
track.
Switch normal and reverse position indication and control
Switch lock indication
Directional route locker indication for each interlocking route
Individual signal clear indication and control for each signal
Signal exit inhibit indication
Signal exit inhibit request and cancel control