METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-123 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
subsystems. Status reporting, information storage and retrieval, alarm processing,
trending and incident and operations reports shall be provided via overhead
displays, ROC consoles, archive media drives and hard disc storage.
As a part of initial system sizing, the SCADA system shall be provided with the
processing capability and memory required for Rail Projects, including
communication circuits, application programs, database, displays, and logs. The
system shall permit database generation and changes, as well as the compiling,
debugging, and integration of new software. Schematic, one-line, pictorial, and
alphanumeric displays shall be generated, altered, or deleted on-line by use of
interactive programs and LCD terminal keyboards. All application programs shall be
implemented with the capacity for all Rail Projects. The SCADA system shall be
designed for ease of expansion and alteration in an economical and efficient
manner, to facilitate future Rail Projects.
The maintainable system life of the SCADA system shall be at last 25 years.
9.11.2. Functional Requirements
1. The SCADA subsystem shall facilitate the transmission of indications and
alarms from the remote terminal units (RTUs) to the ROC and the
transmission of controls from ROC to the RTUs. All transmissions shall be
through the CTS. The SCADA transmissions shall include:
a. Traction power alarm indication and control signals
b. TC alarm, indication and control signals
c. Mechanical equipment, load shed control signals and auxiliary power
alarms
d. Fire detection signals
e. Tunnel ventilation alarm, indication and control signals
f. Communications alarms
g. Miscellaneous electrical/mechanical system status and alarms.
h. Any other interfaces and capabilities required for safe, efficient, and
effective remote operations.
i. All Communications systems control, status/indications and alarms;
j. Passenger station subsystem alarm, indication and control
2. Remote terminal units (RTUs) – See Appendix A - shall be provided to
interface local and remotely located devices with the SCADA subsystem.
Analog input, contact inputs, contact output and local subsystem
communications interfaces shall be provided. The RTU shall provide
isolation between the signal source and the CTS units. The preferred design
is IP based communications (See Appendix B).
3. Redundant server processors shall be provided and configured in a
primary/backup mode to support automatic fail over to the backup processor
upon failure of the primary processor.
4. Signal transmitted from the RTUs to the processors at the ROC shall be
processed to provide monitoring information to all subsystems listed above,
generate commands to be transmitted back to the RTUs, provide information
for displays and alarm processing at the control consoles and store
information and historical data for future processing.