METRO RAIL DESIGN CRITERIA SECTION 9 / SYSTEMS
DE304.09 9-124 Revision 4 : 05/09/12
Metro Baseline Re-Baseline: 04/29/10
5. The SCADA subsystem shall provide monitoring of the seismic detectors
and gas sensors and generate commands for emergency operation
procedures for the control of ventilation fans and dampers. Communication
shall be provided via RTUs on the CTS for data exchange between the ROC
and the CRTs located in the passenger station TC&C rooms, yard, shop and
maintenance areas.
9.11.3. Design Criteria
1. Equipment and associated peripherals for the SCADA subsystem shall
include, but not be limited to, the following:
a. Redundant server processors
b. Data storage peripherals: Disc drives and archive media drives
c. Hard copy printers: High-speed gray scale and color printers
d. Control consoles consisting of:
Dual head, flat screen monitors
Keyboard
Computer interface
Cursor positioning devices.
2. Remote and ROC RTUs shall operate in a full duplex mode with each
continuously scanning and reporting the changes of status of indications and
commands. The RTUs shall utilize reliable, error detecting communications
protocols. Capability shall be provided to scan each data point at an
assignable rate, selectable between one second and 30 seconds per scan
cycle.
3. A computer platform consisting of redundant server processors shall perform
the real-time data acquisition processing, generation of supervisory control
commands, alarm generation, database management, execution of
diagnostic and maintenance programs.
4. Offline simulation and playback functions shall be provided.
5. Hard copy peripherals (e.g. printer) shall interface with the ROC computer.
In addition to the generation of reports, these hard copy peripherals shall be
capable of printing out all alarms that are stored in redundant databases,
including the date and time at which they occur.
6. Alarm displays shall be designed with latching circuitry. An annunciator shall
sound an initial alarm and the visual indication shall be illuminated. The
audible alarm shall have a silencer function. The visual indications shall
remain latched until the alarm is cleared and the indication is reset. Both
audible and visual reset provisions shall be provided on a graphical display
on the SCADA console.
7. Multi color displays with direct manual access to the cursor shall be used for
English language alphanumeric display of status indications, alarms and
controls and graphic display of the schematic diagrams and plans.